Eaton 5PX 3000i RT2U Netpack G2 5PX3000IRTNG2

Dostupnosť: Skladom v eshope

Na predajni: Do 24 hod. po objednaní tovaru

Cena s DPH: 2 356,20 €

5PX3000IRTNG2
Eaton

Popis

GENERAL SPECIFICATIONS

PRODUCT NAME

Eaton 5PX Gen2 UPS

CATALOG NUMBER

5PX3000IRTNG2

PRODUCT LENGTH/DEPTH

603 mm

PRODUCT HEIGHT

85.5 mm

PRODUCT WIDTH

438 mm

PRODUCT WEIGHT

31.7 kg

WARRANTY

3 year on electronics, 2 year on battery

COMPLIANCES

IEC/EN 62040-1

IEC/EN 62040-2

IEC/EN 62040-3

RoHS Compliant

REACH

UL 1778

CSA 22.2

CERTIFICATIONS

CE

cTUVus

EAC

Cm

UKCA

Ukr

KCC

ENERGY STAR certified

MODEL CODE

Eaton 5PX 3000i RT2U Netpack G2

TECHNICKÉ ÚDAJE PRODUKTU

SECONDARY FREQUENCY - MAX

60 Hz

OUTPUT WAVEFORM

Sine wave

MAX NUMBER OF BATTERY PACKS

4

WATTAGE

3000 W

OUTPUT POWER FACTOR

1

FORM FACTOR

Rack/tower

INCLUDES NETWORK CARD

Yes

INPUT CONNECTION

C20

INPUT VOLTAGE - MIN

150 V

OUTPUT VOLTAGE - MAX

240 V

SECONDARY FREQUENCY - MIN

50 Hz

SOFTWARE COMPATIBILITY

Eaton Intelligent Power Manager, Eaton Intelligent Power Protector

BATTERY REPLACEMENT

User replaceable

BATTERY TYPE

Lead-acid maintenance-free (replaceable)

SPECIAL FEATURES

Automatic Voltage Regulation (AVR)|Energy efficient, reduce energy and cooling costs|Delivers clean sinewave output|Provides more real power (watts) to protect more equipment with a Unity power factor (VA=W)|LCD display for real-time status and measurements|Network card and rackmounting kit delivered as standard|Long backup time with up to 4 optional EBM|Meter energy consumption (down to the managed outlet groups)|Versatile product for rack or tower installation|1 slot for optional com card (Network management card, Relay card or Network and Industrial card)|Compatible with Virtual environments (VMware, Hyper-V, Citrix Xen, Redhat)|1 USB port + 1 serial port

OUTPUT VOLTAGE - MIN

200 V

COLOR

Black/silver

EXTENDED BATTERY CAPABILITY

Yes

OUTPUT VOLTAGE RANGE

230 V (+6%/-10%)

TOPOLOGY

Line-interactive

INPUT NOMINAL VOLTAGE

230V default (200/208/220/230/240V)

INPUT FREQUENCY RANGE

47-70 Hz (50 Hz system), 56.5-70 Hz (60 Hz system), 40 Hz in low sensitivity mode

INPUT VOLTAGE - MAX

294 V

VOLTAGE TYPE

AC

PHASE (OUTPUT)

1

BATTERY MANAGEMENT

ABM & Temperature compensated charging method (user selectable), Automatic battery test, deep discharge protection, automatic recognition of external battery units

INTEGRATED FUNCTIONALITY

Network Mangement

AUTO SHUTDOWN FUNCTION

Yes

NUMBER OF OUTPUTS C13

8

NUMBER OF OUTPUTS C19

2

VA RATING

3000 VA

POTENTIAL FREE SWITCH CONTACT

Yes

RECEPTACLE

(8) C13, (2) C19

PHASE (INPUT)

1

PACKAGE CONTENTS

Network Management Card|Input cable|Rack-mounting kit|(2) Supports for tower mounting|Cable locking system|USB cable|Serial cable|(2) IEC-IEC cables|Quickstart guide|Safety instructions

NOISE LEVEL

<40 dB at 1 meter

FEED TYPE

1

RUNTIME GRAPH

View runtime graph

USER INTERFACE

Multilingual graphical LCD display

BATTERY QUANTITY

6

RACK SIZE

2U

VOLTAGE

230V

INPUT CORD LENGTH

1.8m

TEMPERATURE RANGE

0° to 40°C (32° to 104°F), batteries recommended max. 25°C (77°F)

PROTOCOL

SNMP

COMMUNICATION

USB port (HID compliant)|Serial port (RS232)|Mini-terminal block for remote On/Off and Remote Power Off|Mini-terminal block for output relay|Dry contacts (3 outputs, 1 input, optocoupler, DB9)

RELATIVE HUMIDITY

0-90% non-condensing

RACK MOUNTING KIT

Yes

OUTPUT FREQUENCY

50/60 Hz

TYPE OF INTERFACE

Other

PRIMARY FREQUENCY - MIN

47 Hz

BATTERY RATING

12 V / 9 Ah

TYPE

UPS

OUTPUT NOMINAL VOLTAGE

230V default (200/208/220/230/240V)

EXPANSION SLOTS

One slot, network card included

INPUT VOLTAGE RANGE

160-294 V (adjustable to 150 V-294 V)

NOMINAL FREQUENCY

50-60 Hz

PRIMARY FREQUENCY - MAX

70 Hz

ALTITUDE

3000 m